IoT on a boiler house: the twelve points worth measuring

Instrumenting a boiler house is not a data problem, it is a selection problem. Twelve points, sampled properly, tell you more than a hundred that nobody trusts.

Published 17 November 2026 · about 6 minutes · sources listed at the end · Heattech is a system integrator: the equipment belongs to the manufacturers cited, the integration and the measurement are ours.

What "IoT" has to mean here

An industrial site does not need a dashboard that refreshes for the sake of it. It needs a record that can answer three questions months later: what did the plant do, what did the recovery do, and what would have happened without it.

That sets the requirements: values must be time-stamped at the source, buffered locally when the link drops, and sent out through a single outbound connection so the plant firewall never has to open an inbound port. On our demo plant the gateway is an industrial ARM computer (' + link(S['moxa_uc'], 'Moxa UC-4400A') + ') with remote I/O on the signal side (' + link(S['moxa_io'], 'Moxa ioLogik E1200H') + '), posting one gzipped packet per minute.

The twelve points

Twelve points at one-minute resolution is roughly half a million rows a month. That is small enough to keep, and detailed enough to re-derive a saving.

Interval, buffering and trust

One minute is the practical floor: faster than that you are measuring turbulence, slower than five minutes you miss load swings that decide the monthly number. Each reading needs a device-side timestamp, and the gateway needs to hold several days of buffer so a network outage does not become a hole in the evidence.

Trust comes from redundancy, not precision. A fuel flow meter and the utility gas index should agree within a couple of percent; when they do not, the saving claim is not ready. That cross-check is built into the Heattech Pulse package rather than left to a spreadsheet.

Hot water is a different animal

On hot-water plant the key measurement is not stack temperature alone but return water temperature. A condensing boiler or a condensing economizer only condenses when the return is low enough; raise the return by 10 °C and the latent-heat share quietly disappears while the boiler still looks efficient. Log return temperature alongside flue temperature and you can see that trade in the data.

Read more in Hot-water systems: return temperature decides the recovery.