INSIGHT · COMBUSTION · O₂ TRIM

Excess air, O₂ and the cost of a badly tuned burner

Every boiler house we survey has the same first win: the burner is running with more air than it needs, and the excess air is carrying heat up the stack for nothing.

Published 17 November 2026 · about 6 minutes · sources listed at the end · Heattech is a system integrator: the equipment belongs to the manufacturers cited, the integration and the measurement are ours.

One number, three ways of writing it

Combustion needs a minimum amount of air. Anything above that minimum is excess air, and it is normally written three ways: as excess-air percentage, as the oxygen left in the flue (O₂), or as the lambda value (λ = 1 + excess air/100). They are the same fact.

For dry flue gas the conversion is direct: excess air % = O₂ / (20.9 − O₂) × 100. So O₂ 2.2 % is about 12 % excess air, O₂ 2.7 % is about 15 %, and O₂ 3.5 % is about 20 %. Write the target in one unit and show the other, because commissioning sheets, burner manuals and analyser printouts each pick a different one.

We publish our own tuning band the same way: excess air 12–15 % on the demo plant, which is O₂ 2.2–2.7 %, with CO kept under 100 ppm across three load bands (Heattech CT).

Where the money goes

Excess air does two expensive things: it lowers the flame temperature and it increases the mass of gas going up the stack. Both push stack loss up. The practical rule used across the industry is roughly 1 % of fuel for every 20 °C of stack temperature, and a stack temperature that climbs when excess air climbs is the clearest symptom.

Typical commissioning targets, by fuel, are the ones we publish on the Heattech CT page: natural gas 5–10 % excess air, LPG 10–15 %, light fuel oil 15–20 %, heavy fuel oil 20–25 %. Oil needs more air to finish combustion cleanly; gas tolerates much less. Below 5 % on gas, CO rises quickly and the saving becomes a safety problem.

Reading it on a live system

A flue-gas analyser gives you a snapshot. A controller that trims O₂ continuously gives you a system: it measures O₂ in the flue, moves the air damper and the fuel valve together, and holds the curve across the load range. Parallel positioning controllers such as the Fireye NX6300 and compact burner controllers such as the Autoflame Mini Mk9 exist for exactly this job.

Three load bands matter: low fire, mid fire and high fire. A burner tuned only at high fire is usually rich at low fire, and most boilers spend most of their hours at low fire. Our protocol tunes and records all three.

Why tuning and recovery are the same project

Recovery equipment is sized on the flue gas flow and temperature it will see. If the burner is running 20 % excess air, the flue carries more mass than it needs to, the recovery looks bigger on paper than it will be after tuning, and the savings measured afterwards land below the quote. Tuning first makes the recovery quote honest.

That is why our sequence is tune, then recover, then measure — and why the measured number on the savings page is reported against the tuned baseline, not against the pre-tune one.