Recovery cannot repair a burner running at the wrong air-fuel ratio. Heattech CT sets the combustion right — excess-air target, damper and fuel curves — so the flue entering the economizer is already as small as the burner allows.
CT means combustion trim. "Trim" is the industry word for the small continuous correction a controller applies on top of the commissioned air-fuel curve: the curve is fixed at commissioning, the trim moves it a few percent either way as oxygen, stack temperature and load drift. Trim is not a tune-up; a tune-up happens once, trim happens every second. Autoflame and Fireye both use the term this way, and so do we.
Tuning happens on the burner's own control system — typically an Autoflame Mk8 MM with EGA O₂ trim, or the equivalent package on the boiler. We change set points and curves; we never change the flame safeguard logic.
| Setting | Typical target | What it changes |
|---|---|---|
| Excess air | 12 – 15 % (LPG) | The dry flue loss — the single biggest burner-side waste |
| O₂ in flue | 2.2 – 2.7 % | The measurement that proves the excess-air target is held |
| Fuel / air curves | Matched at 3 load bands | Removes the lean-at-low-load, rich-at-high-load drift |
| Flue temperature | As designed per band | Tells you whether recovery still pays at that load |
| CO | < 100 ppm after the tune | Confirms complete combustion — safety, not just efficiency |
| Servo calibration | Verified at each band | Stops the curve from drifting between visits |
Excess air is the working number: it is what the damper and the O₂ trim actually control, and it is quoted as a percentage of the stoichiometric air. The O₂ column is the same setting read on a flue analyser.
| Fuel | Excess air, commissioning target | O₂ in flue | Why this band |
|---|---|---|---|
| Natural gas | 5 – 10 % | 1.0 – 1.9 % | Clean, predictable flame — the tightest band is safe |
| LPG / propane | 10 – 15 % | 1.9 – 2.7 % | Higher carbon content, denser vapour — needs a little more air |
| Light fuel oil | 15 – 20 % | 2.7 – 3.5 % | Atomisation varies with nozzle wear and oil temperature |
| Heavy fuel oil | 20 – 25 % | 3.5 – 4.2 % | Viscosity and sulphur — smoke limits set the floor |
Ranges are standard commissioning targets for packaged industrial boilers; the final setting is bounded by the burner manufacturer's limits and proven by the CO reading after each adjustment. Below 5 % excess air the CO rises fast — a lean flue is not the same as an efficient one.
Trim is a vendor discipline before it is ours. The two names a boiler house will recognise:
| Fireye Nexus | The NX6100 series puts the flame safeguard and the parallel-positioning combustion controller in one package; the NXF4000 model integrates burner management with electronic parallel positioning and O₂ trim in a single controller. Parallel positioning means each actuator (fuel valve, air damper, FGR) has its own positioner, so the air-fuel relationship is set by position, not by a single mechanical linkage. |
|---|---|
| Autoflame | Trim is sold as a control package with an exhaust gas analyser: the EGA reads O₂ (and CO) continuously and the controller corrects the commissioned curve while the boiler runs. Their published large-boiler work is quoted in exactly the terms we use on this site — an O₂ target held across the load range, with the fuel saving stated as a percentage of the bill. |
What that means commercially: trim is a vendor product chosen to match the burner, not something we manufacture. Our contribution is either side of it — metering that proves whether the trim actually held after commissioning, and heat recovery that takes the flue the trim has already tightened. A trim claim with no metering behind it is a sales claim; a trim claim with Heattech Pulse behind it is an invoice.
Sources: Fireye parallel positioning controls · Autoflame Mini Mk9.