Heattech Pulse · METERING & VERIFICATION

Every kilogram, on a meter

A saving you cannot measure is a saving you cannot invoice, defend or repeat. Heattech Pulse is the metering package that turns the flue, the fuel and the condensate into numbers a third party can re-derive.

4streams measured: fuel, steam, flue gas, condensate
1 minsampling interval at the gateway
12samples per compressed packet, one POST per minute
0inbound ports opened at the plant — the gateway only posts out

What is measured, and with what

The instrument list is fixed per site at survey. Nothing enters the saving calculation unless it is on this list, and every channel is time-stamped at the gateway — not in the dashboard.

StreamInstrumentRange / signalWhy it is there
FuelMass flow meter on the fuel line4–20 mA, ±0.5 % of reading The number the gas invoice is calculated from
SteamFlow meter, cross-checked against feedwaterPulse / 4–20 mA Normalises the saving per tonne of steam, not per hour
Flue gas temperatureType K thermocouples, in and out of the economizer0–600 °C Independent check on the heat recovered
Flue gas O₂In-situ O₂ analyser (Autoflame EGA where an Mk8 is fitted)0–21 % O₂ Separates combustion loss from recovery gain
CondensateFlow meter on the economizer drain0–1,000 kg/h Water recovered, and the latent share of the gain
Combustion trimHeattech CT — O₂ trim on the burner controller, correcting damper and air-fuel positionO₂ 0–21 %, held at 2.3–3.0 % Keeps the flue O₂ at target, so excess air is what shrinks — not something the economizer has to compensate for

How the data reaches PULSE

The stack behind Heattech Pulse, named

We do not hide the bill of materials — a customer should know what is bolted to their boiler house:

Field I/OMoxa ioLogik remote I/O modules on the analogue and pulse points (fuel, steam, flue, water). Modbus into the edge computer, so a point can be re-ranged without touching a wire.
Edge computerMoxa UC-4400A — Arm Cortex-A53 quad-core, LTE/5G and Wi-Fi 6E on the cellular models, TPM 2.0, CAN and serial for meters that speak neither Ethernet nor Modbus TCP.
LinkOutbound-only from the plant to the PULSE endpoint. No inbound port is opened at the boiler house, and no control write path exists from the cloud to the burner.
CloudPULSE — the same application that serves the public reference plants: per-minute readings, hourly and daily statistics, the M&V report.

Sources: Moxa UC-4400A series. What we do not publish is how the points are scaled, cross-checked against each other and reconciled into a verified saving — that is the integration work, and it is what a customer pays for.